Chapter 10
IN THIS CHAPTER
Figuring out circuits
Examining conductors and conduit
Taking disconnects and overcurrent protection into account
Protecting your systems from ground faults
Labeling for the benefit of safety personnel
When you install a PV system, you must make safety your top priority. That means giving the wiring and safety components of your PV designs special consideration, particularly during installation. In this chapter, I describe some common wiring and safety components used in PV systems, specifically conductors, conduit, disconnects, overcurrent protection devices, ground fault protection, and labels. (See Chapter 13 for how to size these items.)
A circuit is the path needed to complete the circle the electrons must run in to do useful work. (For instance, in a grid-direct PV system, the DC circuit is the path the electrons take from the PV modules, through the inverter, and back to the modules.) Different conductors, or wires, throughout a PV system connect circuits, and these conductors are commonly placed inside conduit, or pipes, that protect them as they run from one point to the next.
FIGURE 10-1: Different circuits in a PV system.
Note: The NEC® defines conductors based on their role in circuits. For example, the NEC® makes references to grounded current-carrying conductors (for both AC and DC circuits) and grounded conductors (for both types of circuits). I suggest you become familiar with the Code language and terms for your PV installations by digging into the NEC® and picking up a book on understanding the NEC®.
For the components of a PV system (meaning the array, batteries, charge controller, and inverter) to work together and produce energy, something needs to join them together — enter wiring. The wires used to connect all the individual pieces of equipment in a PV system are known as conductors. The PV side of the system has positive and negative conductors, and each one is connected to its respective part of the PV modules.
The most common material for the conductors used in PV systems is copper because it has high conductivity (the ability to pass current) and is compatible with the conductor terminations (the place where the conductors are attached to the disconnects, circuit breakers, inverters, and charge controllers).
Selecting the proper conductor isn’t difficult, so there’s no excuse for ever installing a conductor just because it was in the truck. Numerous conductor types are available, and each one has its proper uses and limitations, as you find out in the following sections.
Standard PV modules come with two copper conductors preinstalled with quick-connect plugs for connection to adjacent modules and to help make the installation process easier. These factory-installed conductors, which are often underground service entrance (USE-2) cables, connect from module to module (or directly to a microinverter, which I describe in Chapter 9) and are secured to the backside of the PV array using specially designed clips and wire ties, as I describe in Chapter 17.
Because USE-2 is often installed along the backside of a PV array as part of the PV source circuit wiring, it gets exposed to some extreme conditions, including full sunlight and temperatures exceeding 60 degrees Celsius (140 degrees Fahrenheit). USE-2 conductors work in these extremes because they’re inherently sunlight-resistant as well as heat- and moisture-resistant.
A double-insulated conductor known as PV wire uses cross-linked polyethylene for the insulation. This durable conductor was born out of the need for a conductor that could be used with a transformer-less inverter (see Chapter 9) because the NEC® requires additional protection in the form of conduit or multiple layers of insulation for the conductors on the PV side of these inverters. The two layers of insulation in PV wire help protect the copper conductors more than the single-insulated USE-2 conductor.
Conductors that leave the junction box or combiner box on their way to the inverter or charge controller are usually transitioned into a standard type of building wiring, such as heat-resistant thermoplastic (THHN) or moisture and heat-resistant thermoplastic (THWN-2). They can be aluminum or copper.
Building wiring is usually used for PV output circuits, inverter input circuits, and inverter output circuits. You can use it on both the DC and AC sides of a PV system, but you need to make sure you protect the conductors from damage by running them inside conduit (see the later related section). Note that building wiring can’t be run in exposed locations because it doesn’t have the sunlight-resistant characteristics of USE-2 and PV wire.
The most widely available conductors for use from the battery bank to the inverter in battery-based systems are moisture-resistant thermoset (RHW), moisture- and heat-resistant thermoplastic (THW), and underground service entrance (USE). All of these conductors are commonly made with copper.
Any conductors used for battery wiring are in corrosive environments, so you need to verify with the manufacturer and the NEC® that the conductor type you want to use is appropriate for the location. Chapter 3 in the NEC® covers wiring methods and materials, so refer to the Code for more info.
All the exposed metal parts of PV systems need a connection to ground, which means you need to connect the PV module frames, racking, and metal boxes to a conductor that’s connected to a large conductor that’s in contact with the earth. (I get into grounding in Chapter 17.) The conductors used to make the ground connections between PV modules are almost always bare copper. After the PV system’s conductors are transitioned into conduit, either bare copper or insulated ground conductors can be used.
Ground wiring can be run with all the circuits mentioned earlier in this chapter: PV source, PV output, inverter input, and inverter output. Using bare ground wire to ground the PV modules is preferable because it’s properly rated for that environment and readily accessible. Using building wiring, like THWN-2, for ground wire in conduit is great; it’s easier to pull and has the appropriate color-coding on the insulation. (I explain the importance of color-coding in Chapter 17.)
With the exception of the PV source circuit wiring, the conductors used in PV systems need proper protection from potential damage; this protection is referred to as conduit. (PV source circuit wiring doesn’t require conduit because NEC® allows you to use USE-2 or PV wire in these locations.) You can see some examples of conduit found in PV systems in Figure 10-2. Conduit can come in a wide range of sizes, as you discover in Chapter 13, and a variety of materials. Selecting the right conduit for the system you’re designing depends on the location where the conduit will be used and any additional NEC® requirements. (Chapter 17 outlines some of the specific requirements surrounding conduit installation in PV systems.)
FIGURE 10-2: Conduit used in PV systems.
You have two main options for conduit: metallic and nonmetallic. Both provide protection for the conductors they house, but they have different installation and usage requirements.
According to the NEC®, you can install PV circuits (I explain what these are in the earlier “Defining the Circuits in a PV System” section) for the PV output circuits inside a building prior to a disconnecting means as long as they remain in metallic conduit. A variety of metallic conduit options are available for use in PV installations, and each one offers excellent physical protection. Two of the more popular metallic conduit types are as follows:
Nonmetalllic conduit is acceptable in PV systems as long as the conduit has the proper ratings (such as UV protection) and is listed for installation in a particular location (such as exposed wet locations). You can use nonmetallic conduit for any of the circuits in PV systems. Common types of nonmetallic conduit include the following:
The conductors used in PV systems carry the current from the array down to the inverter and then to the loads. For safety and maintenance reasons, you need to install a way for those conductors to disconnect themselves from all sources of power. The exact location and specifications for disconnects depend on the specifics of the system installed, but all PV systems, regardless of their size, must possess the ability to disconnect the conductors.
Figure 10-3 shows two types of disconnects used in PV systems:
FIGURE 10-3: A disconnect integrated into an inverter (a) and separate disconnects (b).
According to the NEC®, DC and AC disconnects must be provided to stop power flowing in the conductors and allow for safe access to all components of the PV system. Generally, this guideline means supplying disconnects at the inverter location(s) as well as at points of interconnection with the utility (this last part applies only to utility-interactive systems).
Note: Disconnects can also serve as the form of overcurrent protection, like a circuit breaker that makes the utility interconnection for a utility-interactive inverter. See the next section for the full scoop on overcurrent protection.
When conductors are installed in PV systems, they need protection from the possibility of too much current passing through them. Enter overcurrent protection devices (OCPDs). When too much current begins to pass through a conductor, an OCPD opens the circuit, preventing additional current from passing through until someone manually resets or replaces the device.
The following sections cover the two types of OCPDs used in PV systems — circuit breakers and fuses — so you can get a feeling for exactly how they protect conductors and where you should install them. (I show you how to size these devices in Chapter 13.)
Circuit breakers are the devices you most likely have installed in the main distribution panel at your home. The circuit breakers used in PV systems are very similar. They may have a different look based on the manufacturer, but for the most part they operate in the same way: When too much current passes through a circuit breaker, the breaker trips, opening the circuit and stopping the current from flowing. Most breakers are thermally activated, so they trip when they reach a certain temperature. The nice feature about circuit breakers is that when they trip, you can simply reset them instead of replacing them.
When you’re dealing with a high-voltage DC circuit or when the OCPD needs to be placed outside of a load center, you need to install a fuse. Fuses come in all shapes and sizes, and they can fit any PV system requirement.
Fuses work pretty similarly to circuit breakers, which makes them a good substitute when you can’t use circuit breakers. Inside every fuse is a filament that remains intact as long as it doesn’t get too hot. If too much current passes through the fuse, the fuse overheats and pops, and the current is interrupted. Note: A popped fuse must be replaced; it can’t be reset like a circuit breaker.
Like circuit breakers, fuses have specific listings associated with them. The main one you need to be aware of is the DC rating. Many fuses carry both AC and DC current ratings but at very different voltage levels. You need to make sure you order the fuses with the proper DC voltage and current ratings when you use them on the DC side of a system (typically the PV source circuit).
To help reduce the risk of fires when a PV array has experienced a fault, ground fault protection (GFP) devices have become a requirement for all but a few PV installations. When you deal with grid-direct systems, you need only consider the proper installation techniques because GFP comes standard in grid-direct inverters (see Chapter 9). When you’re working with battery-based systems, however, expect to have an additional component to install. (Fortunately you only have one option in terms of current ratings. Check the NEC® for its specific requirements regarding interrupting faults.)
GFP is added to PV systems at the inverter inside a DC wiring box to reduce the risk of fire if an array’s conductors become compromised. If either the positive or the negative conductor is damaged, that conductor can come into contact with a metal component in the PV system such as a module, the racking, or the inverter. This contact between the conductor (which contains the current from the PV array) and metal pieces allows current to flow and presents a fire (and shock) hazard.
A GFP works by purposely connecting one of the current-carrying conductors across the GFP circuit. This circuit is kept closed through a small-amperage fuse (generally just 1 A). The circuit is looking for any current that’s flowing from one of the current-carrying conductors to ground. Under normal circumstances, there’s no current to ground, but as soon as a wire comes into contact with a grounded portion of the array (anything metallic), current then flows to ground. This improper current flow causes the fuse inside the GFP to pop and a visible sign to appear, like a warning light or a circuit breaker in the off position, indicating the presence of the ground fault. So when the GFP is open, a reference to ground is no longer present for the conductors. This situation is known as floating, and it’s a dangerous one for whoever’s troubleshooting the array.
Proper labeling is growing increasingly important as PV systems become more popular. Inspectors are now requiring PV system installers to do a better job of meeting Article 690 of the NEC®, which lists a number of labeling requirements for PV systems. I outline the exact language needed on system-specific labels in Chapter 18, but in this section, I outline the general requirements and the generic labels needed for every job.
FIGURE 10-4: Sample labels for PV systems.