7
INTERIOR FINISHES FOR WOOD LIGHT FRAME CONSTRUCTION
Completing the Building Enclosure
Increasing Levels of Thermal Insulation
Miscellaneous Finish Carpentry
Flooring and Ceramic Tile Work
COMPLETING THE BUILDING ENCLOSURE
The walls, roofs, and other surfaces of a building that separate the indoors from the outdoors may be referred to as the building envelope or building enclosure. The building enclosure controls the flow of heat, air, and moisture between the interior and exterior. Well-designed and carefully constructed enclosure assemblies help keep a building cooler in summer and warmer in winter by retarding the passage of heat and air through the exterior surfaces of the building. They help keep the occupants of the building more comfortable by moderating the temperatures of the interior surfaces of the building and reducing convective drafts. They reduce the building energy consumption for heating and cooling to a fraction of what it otherwise would be. Furthermore, they prevent the harmful accumulation of condensation within the exterior walls, roof, and other enclosure assemblies of the building.
Insulating the Building Frame
Thermal insulating materials resist the conduction of heat. Thermal insulation is added to virtually all buildings to limit winter heat loss and/or summer cooling loads. A material's resistance to the conduction of heat is measured as thermal resistance, abbreviated as R-value, or, in metric units, as RSI-value (or in many cases, also simply as R-value). A material with a higher R-value is a better insulator than one with a lower R-value. Figure 7.13 lists common thermal insulating materials used in wood light frame buildings and some of their characteristics. Glass fiber batts are the most popular, but all of those listed find use. For a more in-depth discussion of the role of thermal insulation in buildings, see Chapter 16.
Batt insulation comes in 16 in. or 24 in. (406 or 610 mm) widths. It is installed by inserting the insulation between framing members and is held in place either by friction or, if the insulation has a paper or foil facing, by stapling the facing to the framing (Figure 7.14). Loose fill insulation is blown into attic floors or, in insulation retrofits, into wall cavities through holes drilled through the exterior siding. Spray fiber insulation is blown from a nozzle (Figure 7.15). A light spray of water activates a binder that adheres the insulation in place and prevents settlement. Foamed-in-place insulation usually consists of two components sprayed or injected into place, where they react chemically to expand and adhere to the surrounding surfaces (Figure 7.16). Rigid and semi-rigid board insulation are nailed in place over wood framing, or when used around foundations, adhered in place (Figure 5.12). Plastic foam insulation, both spray foam and rigid board, is combustible and releases toxic gasses when it burns. Where these materials face the building interior, most must be covered with gypsum wallboard or some other material that will delay the onset of combustion while occupants exit the building.
(a)
(b)
(c)
(d)
(e)
(a)
(b)
Aerogel insulation consists of a silica gel embedded in a flexible fabric. It is available in blanket form, approximately ¼ inch (6 mm) thick, suitable for both interior and exterior applications. It has a very high insulation value and is very costly. Vacuum insulated panels are made from rigid fumed silica boards that have been evacuated and then sealed within an airtight, vapor-tight foil or polymer wrapping. They are also very expensive, but have the highest available insulation values per unit of thickness of any currently available building insulation product. However, vacuum insulation panels require careful handling during shipping and construction. If the panels are cut or punctured, they lose much of their insulation value. Vacuum insulated panels also gradually lose some portion of their insulation value over time, as air and moisture slowly seep into the panels. Because of their high costs, aerogel and vacuum insulation panels are best suited to applications where limiting dimensions make it impossible to meet required insulation values with other materials.
Increasing Levels of Thermal Insulation
The colder the climate, the greater the amounts of insulation required in the building enclosure to avoid wasteful energy loss. A wall framed with 2 × 4 (38 × 89 mm) studs and filled with glass fiber batt insulation can achieve a thermal resistance of R-13 to R-15 (RSI-2.3 to 2.6). According to current energy code standards, this is adequate only for a residential building in the very southernmost portions of the continental United States and Hawaii. To achieve higher insulation values, either the wall can be framed with 2 × 6 (38 × 140 mm) studs and insulated with thicker batts, or rigid or semi-rigid insulation boards can be added to one side or the other of a 2 × 4 insulated wall (Figure 7.17).
Of the two strategies illustrated in Figure 7.17, the insulation applied continuously across the wall in the right-hand example has the advantage of reducing heat loss caused by thermal bridging. Thermal bridging occurs wherever framing members interrupt the insulation, creating areas of wall with lower thermal resistance and reducing the insulating efficiency of the wall as a whole. Thus, even though the nominal R-value of the right-hand example in the figure is less than that of the one on the left, when the effects of thermal bridging are taken into account, the two are comparable in real-life energy performance. For residential buildings in colder climates, as well as for most commercial buildings, continuous insulation such as this is always required.
Walls may be insulated to levels greater than those illustrated in Figure 7.17 either to meet code requirements in colder climate zones, or, where desired, in excess of code requirements as a way to create an even more energy-efficient building. For example, the thermal enclosure of a building designed to the Passive House (or PassivHaus) standard must be sufficiently efficient such that no major heating or cooling systems are required to maintain the building at comfortable temperatures. (The majority of the heat required to keep a Passive House building warm comes from the body heat of its occupants, waste heat from electrical equipment, and solar gains.) Figure 7.18 illustrates two possible ways to achieve high insulation values in a wood light frame wall. The superinsulated (very high insulation value) wall on the right has an insulation value in the range of what may be required in a Passive House project in a cold climate.
Heat loss due to thermal bridging across the wall cavity can also be reduced with modified framing techniques. Figures 7.19 and 7.20 illustrate details that reduce the area of solid framing at wall corners and headers over doors and window openings. Advanced framing techniques, discussed in Chapter 5, also significantly reduce thermal bridging in the wall frame.
(a)
(b)
(a)
(b)
Insulation continuity can also become compromised where ceiling insulation under a sloped roof must be compressed in the diminishing space between the roof sheathing and the top of the exterior wall, as can be seen in Figure 7.17. A raised-heel roof truss is one way to overcome this problem (Figure 7.21).
Minimum insulation values for other parts of the building enclosure, such as roofs, basement walls, and slabs on grade, are treated similarly, with lower insulation values permitted in milder climates and higher values required in climates that are more severe.
Radiant Barriers
In warmer regions, radiant barriers may be used in roofs and walls to reduce the flow of heat into the building. These are thin sheets or panels faced with a bright metal foil that blocks the transmission of infrared (heat) radiation. Radiant barriers can be installed in various locations within the wall or roof. However, the reflective surface must face an airspace in order to function. In one configuration, air barriers are located close to the exterior side of the wall or roof assembly, in a ventilated airspace. The radiant barrier reflects the very high temperatures experienced by the outermost skin of the building and the ventilated space convectively exhausts accumulated heat. Alternatively, a radiant barrier may be attached to the underside of roof framing in an attic. In this location, the barrier is equally effective at preventing the radiation of heat downward. A potential shortcoming of radiant barriers is their loss of effectiveness over time if the reflective surface becomes dulled by dust, grime, or corrosion.
Vapor Retarders
A vapor retarder (also called, less accurately, a vapor barrier) is a material placed on the warm side of thermal insulation to prevent water vapor (humidity) from diffusing into the insulation where it could condense into liquid. In the International Residential Code, vapor retarders are grouped accordingly to their relative resistance to water vapor diffusion. Class I vapor retarders are the most resistant; that is, they have the lowest vapor permeance. Class II and III retarders are each increasingly permeable.
Where vapor retarders are used, they are normally placed on the interior (warm) side of the insulation. Polyethylene plastic sheet, a Class I vapor retarder, is stapled to the face of wood framing after the insulation has been installed in the framing cavities (Figure 7.14(a)). To further improve its performance (as well as to control air leakage), the edges of the sheets are lapped and taped or sealed, and penetrations at electrical outlets, plumbing, and other such elements are carefully sealed as well. Asphalt-coated kraft paper facing available with many batt insulation products is a Type II vapor retarder (Figure 7.14(b)). The insulation is installed with the paper side facing inward and the paper tabs that extend beyond the edges of the insulation are stapled to the face of the adjacent framing members. Latex paint applied over conventional interior gypsum wallboard is an example of a Class III vapor retarder.
The importance of the vapor retarder in an insulated assembly increases with colder climates. But climate is not the only consideration. For example, the International Residential Code requires Type I or II vapor retarders for buildings in roughly the upper half to two-thirds of the continental United States. However, where exterior walls are designed to be more tolerant of high rates of vapor diffusion without harmful condensation, more permeable Type III vapor retarders may be used. (Such walls may be constructed with ventilated exterior cladding, insulated sheathing, or relatively permeable exterior sheathing products.) In the National Building Code of Canada, the insulated enclosure of small buildings must have vapor retarders comparable in performance to Class I or II.
In mixed or hot climates, the addition of vapor retarders where none is required or use of a vapor retarder with a much lower vapor permeance than needed should be approached with caution. This can lead to the inadvertent entrapment of water within the wall. For more information about vapor retarders in buildings, see Chapter 16.
Air Barriers
Air barriers control the leakage of air through the building enclosure. They significantly reduce building energy consumption and help protect enclosure assemblies from moisture condensation by restricting the infiltration of humid air.
Air barriers appear in some form in all insulated enclosures. Housewraps applied over exterior sheathing are one common way to incorporate an air barrier into wood light frame buildings. Or, when plastic sheeting used as a vapor retarder is carefully sealed against air leakage, it can function effectively as an air barrier. As an alternative to traditional building papers or housewraps, liquid air/weather barrier membranes can be applied to wall and roof sheathing; these provide the necessary moisture resistance and act as highly effective air barriers when combined with special tapes and sealants to seal around openings and penetrations in the wall.
The airtight drywall approach (ADA) relies on the gypsum wallboard (drywall) panels used to finish interior walls and ceilings to create an effective air barrier (Figure 7.22). Careful attention must be given to details of construction with this method: Potential air leakage paths around the edges of gypsum panels and between abutting framing members must be sealed with compressible foam tape gaskets or joint sealants during the installation of these members; gypsum board is applied to all the interior surfaces of the outside walls before the interior partitions are framed, eliminating potential air leaks where these partitions intersect; and gaskets, sealants, or special airtight boxes are used to seal air leakage paths around electrical fixtures and other penetrations.
The ADA requires careful attention to joint sealing throughout rough framing and drywalling operations. A related system, simple caulk and seal, relies on the strategic application of joint sealants after framing and drywalling are complete to achieve much the same result as the ADA. Simple caulk and seal is easier to coordinate, because the joint sealing occurs separately from the work of other trades. However, it may be less successful at eliminating air leakage paths that become concealed and inaccessible before the sealing work takes place.
Many energy codes require blower door testing once the insulation and air barrier components of the building enclosure are fully in place. In this test, a large fan is temporarily installed into an exterior door opening and used to pressurize the entire building interior to a specified level. Calculations are then performed to determine the rate of air leakage through the complete building enclosure. If the leakage rate exceeds that permitted by code, the sources of leakage are sought out and additional testing is performed to bring the building into compliance. The permitted rate of air leakage varies, with buildings in colder regions requiring more airtight enclosures than those in milder ones. The role of the air barrier in the building enclosure is discussed in more detail in Chapter 19.
Infiltration and Ventilation
Reducing the flow of heat and air through the building enclosure reduces energy consumption. However, tightly constructed homes or apartment buildings may exchange so little air with the outdoors that if they are not adequately ventilated, indoor moisture, odors, and chemical pollutants can build up to intolerable or unhealthful levels. Opening a window to ventilate the dwelling is one way to introduce fresh air, but during heating or cooling seasons this wastes fuel. A better solution is a mechanical ventilation system designed to supply fresh air to interior spaces at a controlled and consistent rate. Such a ventilation system may be integrated with a forced-air heating or cooling system, or it may be dedicated solely to satisfying ventilation needs. For greater energy efficiency, a heat recovery ventilator or energy recovery ventilator—devices that recover heat from the air exhausted from the building and add it to the outside air that is drawn in—may be parts of such a system. Nonresidential buildings of wood light frame construction generally require higher rates of ventilation than residential structures, and here, too, low-infiltration construction and appropriately designed ventilation systems are important to maintaining a healthful and comfortable interior environment while also reducing heating and cooling costs.
WALL AND CEILING FINISH
Gypsum-based plaster and drywall finishes have always been the most popular for walls and ceilings in wood frame buildings. Their advantages include substantially lower installed costs than any other types of finishes, adaptability to either painting or wallpapering, and, importantly, a degree of fire resistance that offers considerable protection to a combustible frame. Three-coat gypsum plaster applied to wood strip lath was the prevalent wall and ceiling finish system until the Second World War, when gypsum board (also called drywall) came into increasing use because of its lower material cost, more rapid installation, and utilization of less skilled labor. More recently, veneer plaster systems have been developed that offer surfaces of a quality and durability superior to those of gypsum board, often at comparable prices.
Plaster, veneer plaster, and gypsum board finishes are covered in detail in Chapter 23. Gypsum board remains the favored material for small builders who do all the interior finish work in a building themselves, because the skills and tools it requires are largely those of carpenters rather than plasterers. In geographic areas where there are plenty of skilled plasterers, veneer plaster captures a substantial share of the market. Almost everywhere in North America, there are subcontractors who specialize in gypsum board installation and finishing and who are able to finish the interior surfaces of larger projects, such as apartment buildings, retail stores, and rental office buildings, as well as individual houses, at highly competitive prices.
In most small buildings, all wall and ceiling surfaces are covered with plaster or gypsum board. Even wood paneling should be applied over a gypsum board backup layer, for increased fire resistance. In buildings that require fire walls between dwelling units or fire separation walls between areas with different uses, a gypsum board wall of the required degree of fire resistance can be installed, eliminating the need to employ masons to put up a wall of brick or concrete masonry (Figures 5.67 and 5.68).
MILLWORK AND FINISH CARPENTRY
Millwork (so named because it is manufactured in a planing and molding mill) includes all the wood interior finish components of a building. Millwork is generally produced from much higher-quality wood than that used for framing: The softwoods used are those with fine, uniform grain structure and few defects, such as sugar pine, Ponderosa pine, or poplar. Flooring, stair treads, and millwork intended for transparent finish coatings such as varnish or shellac are customarily made of hardwoods such as red and white oak, cherry, mahogany, or walnut, or of similar quality hardwood plywoods.
Moldings are also produced from high-density plastic foams, parallel strand lumber, and medium-density fiberboard as a way of reducing costs and minimizing moisture expansion and contraction. All these materials must be painted.
The quality of millwork is regulated by the Architectural Woodwork Institute (AWI), which defines three grades: Economy, Custom, and Premium. Economy Grade cabinetry and millwork represents the minimum expectation of quality. Custom Grade provides a well-defined degree of control over the quality of materials, workmanship, and installation and is the most commonly specified grade. Premium is the most expensive grade, and is reserved for the very finest cabinets and millwork.
Millwork is manufactured and delivered to the building site at a very low moisture content, typically about 10 percent, so it is important to protect it from moisture and high humidity before and during installation to avoid swelling and distortions. The humidity within the building is frequently high at the conclusion of plastering or gypsum board work. The framing lumber, concrete work, masonry mortar, plaster, drywall joint compound, and paint are still diffusing large amounts of excess moisture into the interior air. As much of this moisture as possible should be ventilated to the outdoors before finish carpentry (the installation of millwork) commences. Windows should be left open for a few days, and in cool or damp weather the building's heating system should be turned on to raise the interior air temperature and help drive off excess water. In hot, humid weather, the air conditioning system should be activated to dry the air.
Interior Doors
Figure 7.23 illustrates five doors that fall into three general categories: Z-brace, panel, and flush. Z-brace doors, mostly built on site, are used infrequently because they are subject to distortions and large amounts of moisture expansion and contraction in the broad surface of boards whose grain runs perpendicular to the width of the door. Panel doors were developed centuries ago to minimize dimensional changes and distortions caused by the seasonal changes in the moisture content of the wood. They are widely available in ready-made form from millwork dealers. Flush doors are smooth slabs with no surface features except the grain of the wood. They may be either solid core or hollow core. Solid-core doors consist of two veneered faces glued to a solid core of wood blocks or bonded wood chips (Figure 7.24). They are much heavier, stronger, and more resistant to the passage of sound than hollow-core doors and are also more expensive. In residential buildings, their use is usually confined to entrance doors, and because of their natural resistance to fire, doors between car garages and a residence. However, they are frequently installed throughout commercial and institutional buildings, where doors are subject to heavier use. Hollow-core doors have two thin plywood faces separated by an airspace. The airspace is maintained by an interior grid of wood or paperboard spacers to which the veneers are bonded. Flush doors of either type are available in a variety of veneer species, the least expensive of which are intended to be painted.
For speed and economy of installation, most interior doors are furnished prehung, meaning that they have been hinged and fitted to frames at the mill. The carpenter on the site merely tilts the prehung door and frame unit up into the rough opening, plumbs it carefully with a spirit level, shims it with pairs of wood shingle wedges between the finish and rough jambs, and nails it to the studs with finish nails through the jambs (Figure 7.25). Casings are then nailed around the frame on both sides of the partition to close the ragged gap between the door frame and the wall finish (Figure 7.26). To save the labor of applying casings, door units can also be purchased with split jambs that enable the door to be cased at the mill. At the time of installation, each door unit is separated into halves, and the halves are installed from opposite sides of the partition to telescope snugly together before being nailed in place (Figure 7.27).
(a)
(b)
(c)
(d)
Window Casings and Baseboards
Windows are cased in much the same manner as doors (Figures 7.28 and 7.29). After the finish flooring is in place, baseboards (see Figures 7.36K–N and 24.31) are installed to cover the gap between the flooring and the wall finish and to protect the wall finish against damage by feet, furniture legs, and cleaning equipment.
(a)
(b)
(c)
(d)
(e)
(f)
(g)
(h)
(i)
When installing casings or baseboards, the carpenter recesses the heads of finish nails below the surface of the wood, traditionally using a hammer and a nail set (a hardened steel punch), or, as is more likely today, a powered finish nail gun. Later, the painters will fill these nail holes with a paste filler and sand the surface smooth after the filler has dried so that the holes will be invisible in the painted woodwork. For transparent wood finishes, nail holes are usually filled after the finishes have been applied, using wax-based fillers that are supplied in a range of colors to match the full range of wood species.
The nails in casings and baseboards must reach through the plaster or gypsum board to penetrate the framing members beneath in order to make a secure attachment. Eight- or ten-penny finish or casing nails are customarily used.
Cabinets
Cabinets for kitchens, bathrooms, bedrooms, workrooms, and other spaces may be either custom- or factory-fabricated. Custom wood cabinets are fabricated in specialty woodworking shops according to drawings and specifications prepared individually for each project. Like quality millwork, custom cabinets are constructed to AWI specifications, usually Premium or Custom Grade. Less expensive, manufactured wood cabinets are factory-manufactured to standard sizes and configurations. Both types of cabinets are usually delivered to the construction site fully finished.
On the construction site, cabinets are installed by shimming against wall and floor surfaces as necessary to make them level and screwing through the backs of the cabinet units into the wall studs (Figures 7.30 and 7.31). The tops are then attached with screws driven up from the cabinets beneath. Kitchen and bath countertops are cut out for built-in sinks and lavatories, which are subsequently installed by the plumber.
Finish Stairs
Finish stairs are either constructed in place (Figures 7.32 and 7.33) or shop built (Figures 7.34 and 7.35). Shop-built stairs tend to be less expensive to build and easier to install. Constructing stairs on site requires highly skilled carpenters but allows stairs to be built to any configuration and fitted more closely to framing or finish irregularities. Stair treads are usually made of wear-resistant hardwoods such as oak or maple. Risers and stringers may be made of any reasonably hard wood, such as oak, maple, or Douglas fir.
(a)
(b)
Three openings are required in stair-cases; the first is the door thro' which one goes up to the staircase, which the less it is hid to them that enter into the house, so much the more it is to be commended. And it would please me much, if it was in a place, where before that one comes to it, the most beautiful part of the house was seen; because it makes the house (even tho' small) seem very large; but however, let it be manifest, and easily found. The second opening is the windows that are necessary to give light to the steps; they ought to be in the middle, and high, that the light may be spread equally every where alike. The third is the opening thro' which one enters into the floor above; this ought to lead us into ample, beautiful, and adorned places.
—Andrea Palladio, The Four Books of Architecture, 1570
Miscellaneous Finish Carpentry
Finish carpenters install dozens of miscellaneous items in the average building: closet shelves and poles, pantry shelving, bookshelves, wood paneling, chair rails, picture rails, ceiling moldings, mantelpieces, laundry chutes, folding attic stairs, access hatches, door hardware, weatherstripping, doorstops, and bath accessories (towel bars, paper holders, and so on). Many of these items are available ready-made from millwork and hardware suppliers (Figures 7.36 and 7.37), but others have to be crafted by the carpenter.
FLOORING AND CERAMIC TILE WORK
Before finish flooring can be installed, the subfloor is scraped free of plaster droppings and swept thoroughly. Underlayment panels of C–C Plugged plywood or particleboard (in areas destined for resilient flooring materials or carpeting) are glued and nailed over the subfloor, their joints staggered with those in the subfloor to eliminate weak spots. The thicknesses of the underlayment panels are chosen to make the finished floor surfaces as nearly equal in level as possible at junctions between different flooring materials.
In multistory wood light frame commercial and apartment buildings, specially formulated lightweight poured gypsum or portland cement underlayment is often placed over the subfloor. This has a threefold function: It provides a smooth, level surface for finish floor materials; it furnishes additional fire resistance to the floor construction; and it reduces the transmission of sound through the floor to the apartment or office below. The gypsum or concrete is formulated with superplasticizer additives that make it self-leveling as it is applied (Figure 7.38). A minimum thickness is ¾ inch (19 mm). Poured underlayments are also used to level floors in older buildings, to add fire and sound resistance to precast concrete floors, and to embed plastic tubing or electric resistance wires for in-floor radiant heat.
Floor finishing operations require cleanliness and freedom from traffic, so members of other trades are banished from the area as the flooring materials are applied. Hardwood flooring is sanded level and smooth after installation, then vacuumed to remove the sanding dust. The finish coatings are applied in as dust-free an atmosphere as possible to avoid embedded specks. Resilient-flooring installers vacuum the underlayment meticulously so that particles of dirt will not become trapped beneath the thin flooring and cause small bumps in the surface. The finished floors are often covered with heavy sheet or thin board material to protect them during the final few days of construction activity. Carpet installation is less sensitive to dust, and the installed carpets are less prone to damage than hardwood and resilient floorings, but temporary coverings are applied as necessary to protect the carpet from paint spills and water stains.
The application of ceramic tile to a portland cement plaster base coat over metal lath for a shower stall is illustrated in Figure 7.39, and finished ceramic tile work is shown in Figure 7.40. Cementitious backer board may be used as a less costly substitute for a cement plaster base coat (Figure 24.28). Wood flooring installation is depicted in Figures 24.31 and 24.32. A finished hardwood floor is shown in Figures 7.41 and 24.33. The installation of ceramic tile and finish flooring materials is covered in more detail in Chapters 23 and 24.
FINISHING TOUCHES
When flooring and painting are finished, the plumbers install and activate the lavatories, water closets, tubs, sinks, and shower fixtures. Gas lines are connected to appliances and the main gas valve is opened. The electricians connect the wiring for the heating and air conditioning equipment and (if electric) water heater; mount the receptacles, switches, and lighting fixtures; and put metal or plastic cover plates on the switches and receptacles. The electrical circuits are energized and checked to be sure that they work. The smoke, heat, and carbon monoxide alarms required by most codes in residential structures, are also connected and tested by the electricians, along with any communications, entertainment, and security system wiring. The heating and air conditioning system is completed with the installation of air grills and registers, or with the mounting of metal convector covers, then turned on and tested. Painted surfaces that have been scuffed or marred are touched up, and last-minute problems are identified and corrected through cooperative effort by the contractors, the owner of the building, and the architect. The building inspector is called in for a final inspection and issuance of an occupancy permit. After a thorough cleaning, the building is ready for use.
1. List the sequence of operations required to complete the interior of a wood light frame building and explain the logic of the order in which these operations occur.
2. What are some alternative ways of insulating the walls of a wood light frame building to R-values beyond the range normally possible with ordinary 2 × 4 (38 × 89 mm) studs?
3. Why are plaster and gypsum board so popular as interior wall finishes in wood frame buildings? List as many reasons as possible.
4. What is the level of humidity in a building at the time installation of the interior wall finishes is completed? Why? What should be done about this and why?
5. Summarize the most important things to keep in mind when designing a stair.
6. Describe the function of thermal insulation. When and where is it used?
7. Describe the function of a vapor barrier. When and where is it used?
8. Describe the purpose of an air barrier. When and where is it used?
1. Design and detail a fireplace for a building that you are designing, using the information provided in this chapter to work out the exact dimensions and the information in Chapter 8 to help in detailing the masonry.
2. Design and detail a stairway for a building that you are designing. Provide complete dimensions.
3. Visit a wood frame building that you admire. Make a list of the interior finish materials and components, including finishes and species of wood where possible. How does each material and component contribute to the overall feeling of the building? How do they relate to one another?
4. Make measured drawings of millwork details in an older building that you admire. Analyze each detail to discover its logic. What woods were used and how were they sawn? How were they finished?
Architectural Woodwork Institute. AWI Quality Standards Illustrated. Reston, VA, updated regularly.
Every detail of every grade of interior woodwork and cabinetry is illustrated and described in this thick volume.
Dietz, Albert G. H. Dwelling House Construction (5th ed.). Cambridge, MA, MIT Press, 1990.
This classic text has extensive chapters with clear illustrations concerning chimneys and fireplaces, insulation, wallboard, lath and plaster, and interior finish carpentry.
Lstiburek, Joseph. Builder's Guide to Cold Climates. Westford, MA, Building Science Corporation, 2006.
This guide, along with companion guides for other major climate zones, explains the roles of insulation, vapor retarders, and air barriers in the performance of the building enclosure, and provides guidelines for the construction of energy-efficient and weather-resistant homes.
Thallon, Rob. Graphic Guide to Interior Details: For Builders and Designers. Newtown, CT, Taunton Press, 2004.
Profusely illustrated, clearly written, and encyclopedic in scope, this book offers complete guidance on interior finishing of wood light frame buildings.
Interior Finishes for Wood Light Frame Construction
Author's supplementary web site: www.ianosbackfill.com/07_interior_finishes_for_wood_light_frame_construction
Thermal Insulation and Vapor Retarder
Building Science Corporation: www.buildingscience.com
Dow Chemical rigid and spray foam insulation: www.dow.com
Gypsum Association: www.gypsum.org
Icynene Corporation spray -foam insulation: www.icynene.com
Owens Corning insulation products: www.owenscorning.com
Passive House Institute (International): www.passiv.de/en/
Passive House Institute: www.passivehouse.us, www.passivehouse.ca, www.passivhaus.org.uk/, www.passiv.de/en/
Wall and Ceiling Finish
USG gypsum products: www.usg.com
Millwork and Finish
Architectural Woodwork Institute: www.awinet.org
Hardwood Plywood & Veneer Association: www.hpva.org
Jeld-Wen Windows & Doors: www.jeld-wen.com
Window and Door Manufacturers Association: www.wdma.org
Proportioning Fireplaces
Buckley Rumford Company: www.rumford.com
Flooring and Ceramic Tile Work
American Olean Tile: www.americanolean.com
Tile Council of America: www.tileusa.com